Failure Cause Analysis of Valve-Regulated Lead-Acid Battery on Fire in Communication Equipment Room

2026-01-7022

2/27/2026

Authors
Abstract
Content
This paper carried out the fire failure analysis of valve-regulated lead-acid battery in communication equipment room. Through disassembly and observation of the battery and iron frame of battery cabinet in the area of fire origin, we obtained the key residual traces and used the physical and chemical analysis methods such as macroscopic/microscopic morphology, EDS, X-ray and metallographic, it was finally judged that the leakage of the battery electrolyte lead to the connection of the battery electrode plate and the iron frame and subsequently the electric heating fault caused the fire accident. Furthermore, we put forward some suggestions according to the existing problems, which may contribute to the prevention of similar failures.