With the rapid development of information technology, electronic devices in
aerospace, data centers and other fields have faced increasingly severe thermal
runaway issues. Two-phase heat transfer technology, with its superior heat
dissipation performance, has attracted growing attention and research. A test
rig was established to investigate the flow boiling characteristics of R134A
within rectangular enhanced flow channels. The test conditions are listed below:
heat load ranging from 100W to 3000W, vapor quality from 0.05 to 0.7, and flow
rate from 5 L/h to 240 L/h. The results indicate: With the increase of inlet
flow rate, The phase change pressure drop gradually increases within the
rectangular enhanced flow channels. Similarly, the relationship holds true for
phase change pressure drop and cold plate heat load, showing a distinct linear
relationship. Under constant heat load, the phase change flow resistance within
rectangular enhanced flow channels gradually decreases with increasing the vapor
quality. The pressure drop changes dramatically when the vapor quality is below
0.3 and becomes significantly more gradual when the vapor quality exceeds 0.4.
Under the test conditions, the maximum density of heat flux is approximately 230
W/cm^2, corresponding to a maximum temperature rise of about 22°C
in the heating unit. The equivalent maximum two-phase heat transfer coefficient
exceeds 12,000 W/(m^2K). When the cold plate outlet vapor quality is
between 0.4 and 0.7, the flow resistance within the rectangular enhanced flow
channels is relatively low, and the cooling performance is relatively high. It
is recommended that two phase system should be designed within this vapor
quality range.